Funtional DescriptionMotor Data Adjustment
6
63
KEB COMBIVERT F5-G / B
Name: Basis
23.01.02
Chapter Section PageDate
© KEB Antriebstechnik, 2002
All rights reserved
ANTRIEBSTECHNIK
KEB Antriebstechnik
GmbH & Co. KG
Schneeberg
Made in
Germany
-Mot IP IM W.KI. °C kg
Hz V
cos
/Y
1/min
UV
~Mot Hz Nm mm
FL
M
Br
I
Sp max
DK 160 L 4 F I /TW150
96/1632804/ 001
3 55 B 3 F 40 127
VDE 053 0
15,0 KW
ϕ
50 230/400
0,86
1455
230/400
350
49,5/28,5 A
IGR 05B 2500 Imp
5V D0/RS 6xTTL
dr.1
dr.0
dr.5
dr.4
dr.2
6.6 Motor Data
Adjustment
Fig. 6.6.1 Example of a motor name plate
6.6.1 Motor Name Plate
The adjustment of the correct motor data is important for many inverter functions,
since calculations are derived from it, which the inverter requires to achieve the best
possible results in the control of Boost and slip compensation.
6.6.2 Motor Data from
the Name Plate
(dr.0...dr.5)
Following parameters can be taken directly from the name plate (see above) and
entered:
- dr.0 Rated motor current 0.0...710.0 A (Star-/Delta-connection)
- dr.1 Rated motor speed 0...64000 rpm
- dr.2 Rated motor voltage 120...500 V (Star-/Delta-connection)
- dr.3 Rated motor power 0.35...400.00 kW
- dr.4 Rated motor power factor cos(phi) 0.00...1.00
- dr.5 Rated motor frequency 0...1600.0 Hz
dr.3
Parameter dr.0 and dr.2 are always to be adjusted according to the used
wiring (star/delta). For above stated motor name plate that is 230 V / 49.5 A
at delta-connection and 400 V / 28.5 at star-connection