Functional Description Protective Functions
Param. Adr.
min
max
default
ENTER
PROG.
R/W
Step
A
B
C
Used Parameters
Pn.22 0416h ✔✔✔ 0 7 1 1 bit-coded
Pn.23 0417h ✔ - ✔ 0 4095 1 0 -
Pn.24 0418h ✔✔- 0 % 200 % 1 % 140 % % referring to inverter rated current
Pn.25 0419h ✔✔- 200 V 800 V 1 V 375/720 V depending on voltage class
uF.15 050Fh ✔ -- 0 2 1 1 -
Fig. 6.7.1.b Example for ramp stop function
Actual frequency (ru.3)
Inverter status (ru.0)
Actual utilization (ru.13)
max. ramp current Pn.24
Acceleration stop
Actual frequency (ru.3)
Inverter status (ru.0)
DC-link voltage (ru.18)
Deceleration stop (U)
max. DC-voltage Pn.25