Chapter
Functional DescriptionSpecial Functions
Param. Adr.
min
max
default
ENTER
PROG.
R/W
Step
Comparison level 0...7
(LE.0...LE.7)
LE.0...LE.7 define the level for the switching conditions 37/38 („timer > level“). If the
timer exceeds the adjusted value the switching condition is set. A level in the range of
-10.737.418,24 bis 10.737.418,23 can be adjusted. But only values of 0...655,34 are
sensible for the counter.
Used Parameters
ru.43 022Bh ✔ - - 0,00 655,35 0,01 0,00 -
ru.44 022Ch ✔ - - 0,00 655,35 0,01 0,00 -
LE.0 0D00h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.1 0D01h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.2 0D02h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.3 0D03h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.4 0D04h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.5 0D05h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.6 0D06h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.7 0D07h ✔✔- -10737418,24 10737418,23 0,01 0 -
LE.17 0D11h ✔ - ✔ 0 4095 1 0 bitcoded
LE.18 0D12h ✔ - ✔ 0710-
LE.19 0D13h ✔ - ✔ 0 4095 1 0 bitcoded
LE.20 0D14h ✔ - ✔ 031116-
LE.21 0D15h ✔ -- 0 31 1 0 -
LE.22 0D16h ✔ - ✔ 0 4095 1 0 bitcoded
LE.23 0D17h ✔ - ✔ 0710-
LE.24 0D18h ✔ - ✔ 0 4095 1 0 bitcoded
LE.25 0D19h ✔ - ✔ 031116-
LE.26 0D1Ah ✔ -- 0 31 1 0 -
Timer Reset condition
(LE.20/25)
According to following table the conditions can be defined under which the timer is
reset in addition to the inputs. The individual conditions are OR-operated.
Bit -No. Decimal value Condition
0 1 Modulation on
1 2 Modulation off
2 4 Setpoint frequency = Actual frequency
3 8 Change of parameter set
4 16 Power-On-Reset