Initial Start-up Start-up
Section PageDate Chapter
7.2.4 Testing of Drive
For the drive to always allow a save controlling through the inverter, carry out the
following test under the most adverse operating conditions.
Picture 7.2.4 Testing of drive
No
Ye s
Does the drive run with the
selected direction of rotation?
Testing of drive
Switch release and adjust
direction of rotation
Adjust low set value
check phase sequence of
motor cable, if necessary,
change
Put the drive in all possible operating
conditions of the application
Was an error triggered?
see Error Assistance
Chapter 9
Test OK!
no
yes