7 2
KEB COMBIVERT F5-G / B
4
Name: Basis
01.02.02
© KEB Antriebstechnik, 2002
All Rights reserved
Initial Start-upStart-up
Chapter Section Page Date
7.2.2 Basic Settings in
the CP-Mode
After switch-on with factory setting the inverter is in the CP-Mode. The preadjusted
values can be used for 90 % of all applications at the initial start-up. However, the
following parameters should be checked and, if necessary, adjusted.
þ Corner frequency CP.16
þ Minimum and maximum frequency CP.10/CP.11
þ Acceleration and decelerationtimes CP.12/CP.13
þ Boost CP.15
þ Activation of the Motor PTC detection, if a PTC is attached
7.2.3 Set value
selection
After the basic settings have been made, it must now be determined how the set
value input is done.
Set value input
In CP-
or
Application Mode?
Via
terminal strip
or
operator?
Via
voltage signal
or
current signal?
0...20mA
or
4...20mA?
CP.35 to value „0“;
terminal X2A.1/2
or/and X2A.3/4
CP.35 to value „1“;
current signal
at terminal X2A.1/2
CP.35 to value „2“;
current signal
at terminal X2A.1/2
Switch terminal
X2A.10 and adjust
frequency with
CP.19
see Chap. 6.4
CP-Mode
Operator
Terminal strip
0...10V Current signal
0...20mA
4...20mA
Picture 7.2.3 Setvalue input