KEB COMBIVERT F5-G / B
Name: Basis
04.12.01
4
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section PageDate
4.3.5 Basic Adjustment
of the Drive
Intermediate circuit voltage/
Peak value
Output voltage
Minimum frequency
Maximum frequency
f
U
REF
CP.11
CP.10
0V 10V
CP.8 makes it possible to recognize short-time voltage rises within an operating cycle.
For that the highest value of CP.7 is stored in CP.8. The peak value memory can be
cleared by pressing the UP, DOWN or ENTER key or over bus by writing any value
you like to the address of CP.8. The switch off of the inverter also clears the memory.
Display of the actual output voltage in volt.
The following parameters determine the fundamental operating data of the drive. They
should be checked and/or adapted to the application.
With this frequency the inverter operates without presetting an analog set value.
Internal limiting of the fixed frequencies CP.19…CP.21.
Adjustment range: 0...400 Hz
Resolution: 0,0125 Hz
Factory setting: 0,0 Hz
With this frequency the inverter operates with maximum analog set value.
Internal limiting of the fixed frequencies CP.19…CP.21.
Adjustment range: 0...400 Hz
Resolution: 0,0125 Hz
Factory setting: 70 Hz