Name: Basis
04.12.01
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section Page Date
"Forward Acceleration" drive accelerates with direction of rotation
forward .
"Forward Deceleration" drive decelerates with direction of rotation
forward.
"Reverse Acceleration" drive accelerates with direction of rotation
reverse.
"Reverse Deceleration" drive decelerates with direction of rotation
reverse.
"Forward Constant" drive runs with a constant speed and direction
of rotation forward.
"Reverse Constant" drive runs with constant speed and direction of
rotation reverse.
Other status messages are described at the parameters, where they occur.
Apparent current Display of the actual apparent current in ampere.
Intermediate circuit voltage
Display of actual DC voltage in volt.
Typical calues:
CP.5 makes it possible to recognize the max. apparent current. For that the highest
value of CP.4 is stored in CP.5. The peak value memory can be cleared by pressing
the UP, DOWN or ENTER key or over bus by writing any value you like to the address
of CP.5. The switch off of the inverter also clears the memory.
Apparent current /
Peak value
Utilization Display of the actual inverter rate of utilization in percent. 100% rate of utilization is equal
to the inverter rated current. Only positive values are displayed, meaning there is no
differentiation between motor and regenerative operation.
V-class Normal operation Over volt. (E.OP) Under volt. (E.UP)
230 V 300…330 V DC approx. 400 V DC approx. 216 V DC
400 V 530…620 V DC approx. 800 V DC approx. 240 V DC