KEB COMBIVERT F5-G / B
Name: Basis
04.12.01
4
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section PageDate
Password
FUNC
ENTER
UP
Enabling the CP-
Parameter
FUNC
ENTER
UP
Password
Barring the
CP-Parameter
4.3.3 Password Input
Ex works the frequency inverter is supplied without password protection, this means
that all changeable parameters can be adjusted. After parameterizing the unit can be
barred against unauthorized access (Passwords: see chapter 4.2). The adjusted mode
is stored.
The parameters below serve for thecontrolling of the frequency inverter during
operation.
Display of the actual output frequency with a resolution of 0.0125 Hz. The operator
displays additionally „noP“ and „LS“ if the control release or the direction of rotation
are not switched (see CP.3). The rotation of the inverter is indicated by the sign.
Output frequency 18.3 Hz, rotation forward
Examples:
Output frequency 18.3 Hz, rotation reverse
4.3.4 Operating Display
Actual frequency display
Inverter status display The status display shows the actual working conditions of the inverter. Possible
displays and their meanings are:
"no Operation" control release not bridged, modulation switched
off, output voltage = 0 V, drive is not controlled.
"Low Speed" no rotation preset, modulation switched off, output
voltage = 0 V, drive is not controlled.
Display of actually set frequency. The indication is done in the same manner as at
CP.1. For control reasons the set frequency is displayed even if control release or
direction of rotation are not switched. If no direction of rotation is set, the set frequency
for clockwise rotation (forward) is displayed.
Set frequency