4 3
KEB COMBIVERT F5-G / B
4
Name: Basis
04.12.01
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section Page Date
The following list shows the CP-parameter group predefined by us. The definition
of the CP-parameters is done in the User-Definition-Parameters (ud). How you can
define your own parameters is described in Chapter 6.13.
4.3.2 Factory Setting
1)
Enter-Parameter
2)
depending on power circuit
Display Parameter Setting range Resolution Factory setting Appl. Parameter
CP. 0 Password input 0…9999 1 – ud.1 / 0801h
CP. 1 Actual frequency display – 0,0125 Hz – ru.3 / 0203h
CP. 2 Set frequency display – 0,0125 Hz – ru.1 / 0201h
CP. 3 Inverter status display – – – ru.0 / 0200h
CP. 4 Apparent current – 0,1 A – ru.15 / 020Fh
CP. 5 Apparent current / Peak value – 0,1 A – ru.16 / 0210h
CP. 6 Utilization – 1 % – ru.13 / 020Dh
CP. 7 Intermediate circuit voltage – 1 V – ru.18 / 0212h
CP. 8 Intermediate circuit voltage/
Peak value – 1 V – ru.19 / 0213h
CP. 9 Output voltage – 1 V – ru.20 / 0214h
CP.10 Minimal frequency 0…400 Hz 0,0125 Hz 0 Hz op.6 / 0306h
CP.11 Maximal frequency 0…400 Hz 0,0125 Hz 70 Hz op.10 / 030Ah
CP.12 Acceleration time 0,00…300,00 s 0,01 s 5,00 s op.28 / 031Ch
CP.13 Deceleration time (-1 = CP.12) -0,01; 0,00…300,00s 0,01 s 5,00 s op.30 / 031Eh
CP.14 S-curve time 0,00 (off)…5,00 s 0,01 s 0,00 s (off) op.32 / 0320h
CP.15 Boost 0,0…25,5 % 0,1 % 2,0 % uf.1 / 0501h
CP.16 Rated frequency 0…400 Hz 0,0125 Hz 50 Hz uf.0 / 0500h
CP.17
1)
Voltage stabilization 1…650 V (off) 1 V 650 (off) uf.9 / 0509h
CP.18
1)
Carrier frequency 0…4
2)
1–
2)
uf.11 / 050Bh
CP.19 Fixed frequency 1 -400...400 Hz 0,0125 Hz 5 Hz op.21 / 0315h
CP.20 Fixed frequency 2 -400...400 Hz 0,0125 Hz 50 Hz op.22 / 0316h
CP.21 Fixed frequency 3 -400...400 Hz 0,0125 Hz 70 Hz op.23 / 0317h
CP.22
1)
DC-braking / Mode 0…9 1 7 pn.28 / 041Ch
CP.23 DC-braking / Time 0,00…100,00 s 0,01 s 10,00 s pn.30 / 041Eh
CP.24 Max. ramp current 0…200 % 1 % 140 % pn.24 / 0418h
CP.25 Max. constant current 0…200 % (off) 1 % 200 % (off) pn.20 / 0414h
CP.26
1)
Speed search condition 0…15 1 8 pn.26 / 041Ah
CP.27 Quick stop time 0,00…300,00 s 0,01 s 2,00 s pn.60 / 043Ch
CP.28 Reaction of ext. overtemperature 0…7 1 7 pn.12 / 040Ch
CP.29
1)
Analog output 1 / Function 0…12 1 2 an.31 / 0A1Fh
CP.30 Analog output 1 / Amplification -20,00…20,00 0,01 1,00 an.33 / 0A21h
CP.31
1)
Relay output 1 / function 0…42 1 4 do.2 / 0C02h
CP.32
1)
Relay output 2 / function 0…42 1 27 do.3 / 0C03h
CP.33 Relay output 2 / switching level -30000,00…30000,00 0,01 4,00 le.3 / 0D03h
CP.34
1)
Source of rotation direction 0…9 1 2 op.1 / 0301h
CP.35
1)
AN1 interface selection 0…2 1 0 an.0 / 0A00h
CP.36 AN1 zero point hysteresis -10,0…10,0 % 0,1 % 0,2 % an.4 / 0A04h