Analog ouput 1 / Function CP.32 defines the function of analog output 1.
Value Function
0 absolute actual value 100 Hz
1 absolute set value 100 Hz
2 actual value ru.7 ±100 Hz
3 set value ru.1 ±100 Hz
4 output voltage ru.20 500 V
5 DC voltage ru.18 1000 V
6 apparent current ru.15 2 • I
rated
7 active current ru.17 2 • ±I
rated
8 digital An.32/An.37/An.42 100 %
9 external PID output ru.52 ±100 %
10 absolute ext. PID output ru.52 100 %
11 absolute active current ru.17 2 • I
rated
12 power mod. temperature ru.38 100°C
13 motor temperature 0...100 °C
14-18 application mode only
19 ramp output frequency 0...±100 Hz
20 absolute ramp output frequency 0...100 Hz
Analog output 1 /
Amplification
10V
CP.30
100%
-100%
100%
-100%
in
out
Setting aid:
The analog output shall give
out +10 V at 70 Hz instead
at 100 Hz:
100 Hz
CP.30 = –––––– = 1,43
70 Hz
With the amplification the output voltage of the analog output can be tuned the signal
to be given out. An amplification of 1 corresponds to ±100 % = +10 V.
Adjustment range: 0...20
Resolution: 1
Factory setting: 2
Note: Enter-Parameter
Adjustment range: -20,00...20,00
Resolution: 0,01
Factory setting: 1,00