KEB COMBIVERT F5-G / B
Name: Basis
04.12.01
4
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section PageDate
Relay output 1 / Function
Relay output 2 / Function
CP.31 and CP.32 determine the function of the two outputs.
CP.31 for relay output 1 (terminal X2A.24...X2A.26)
CP.32 for relay output 2 (terminal X2A.27...X2A.29)
The switching level of CP.32 is CP.33!
Value Function
0 No function (generelly off)
1 Generelly on
2 Run signal; also by DC-braking
3 Ready signal (no error)
4 Fault relay
5 Fault relay (not at under voltage error)
6 Warning or error message at abnormal stopping
7 Overload alert signal
8 Overtemperature alert signal power modules
9 External Overload alert signal motor
10 Only application-mode
11 Excess-temperature alert signal interior OHI
12 Cable breakage 4...20 mA on analog input 1
13 Only application-mode
14 Max. constant current (stall, CP.25) exceeded
15 Max. ramp current (LA-Stop CP.24) exceeded
16 DC-braking active
17-19 Only application-mode
20 Actual value=set value (CP.3=Fcon, rcon; not at noP, LS error,SSF)
21 Accelerate (CP.3 = FAcc, rAcc, LAS)
22 Decelerate (CP.3 = FdEc, rdEc, LdS)
23 Real direction of rotation = set direction of rotation
24 Utilization (CP.6) > 100% (only CP.31)
25 Active current > switching level (only CP.32)
26 Intermediate circuit voltage (CP.7)>switching level (only CP.32)
27 Real value (CP.1) > switching level (only CP.32)
28 Set value (CP.2) > switching level (only CP.32)
29/30 Only application-mode
31 Absolut set value on AN1 > switching level (only CP.32)
32 Absolut set value on AN2 > switching level (only CP.32)
33 Only application-mode
34 Set value on AN1 > switching level (only CP.32)
35 Set value on AN2 > switching level (only CP.32)
36-39 Only application-mode
40 Hardware current limit activated
41 Modulation on-signal
42-43 Only application-mode
44 Inverter status (CP.3) = switching level
45 Power module temperatur > Level
46 Motor temperatur > Level
47 Ramp output frequency > Level
48 Apparent current (CP.4) > Level
49 Clockwise rotation (not at noP, LS, abnormal stopping, Fehler)
50 Counter clockwise (not at noP, LS, abnormal stopping, Fehler)
51-62 Only application-mode
63 Absolut ANOUT1 > switching level
64 Absolut ANOUT2 > switching level
65 ANOUT1 > switching level
66 ANOUT2 > switching level
67-68 Only application-mode