4 3
KEB COMBIVERT F5-G / B
18
Name: Basis
04.12.01
CP - Parameter
© KEB Antriebstechnik, 2001
All Rights reserved
Operation
Chapter Section Page Date
Relay output 2 /
Switching level
This parameter determines the switching point for the relay output 2 (CP.32). After the
switching of the relay, the value can move within a window (hysteresis), without the
relay dropping off. Since the operator can display only 5 characters, the last digits are
not represented in the case of higher values.
Adjustment range: -30000,00...30000,00
Resolution: 0,01
Factory setting: 4,00
Hysteresis:
Frequency: 0,5 Hz
Voltage: 1 V
Analog values: 0,5 %
Current: 0,5 A
Temperature 1 °C
Factory setting CP.31: 4
Factory setting CP.32: 27