49
Generalcontrolcardparameters(operatorfunctionality)
Parameter Id-Text Name CANSDOIndex
os14 store state 0x208E
Subindex 0
Object type Variable
Data length unsigned Byte
Access Read write
Meaning By writing of value "0" non-volatile parameters are immediately stored.
After the storing the status changes to value "1". If at the end of down-
loadlists inCOMBIVIS rstvalue"0" andthen value"1"iswritten,
COMBIVIS transmits the value as long as the inverter has completed
the storage.
Coding
0
busy
1
completed
2
off
Parameter Id-Text Name CANSDOIndex
os15 store mode 0x208F
Subindex 0
Object type Variable
Data length unsigned Byte
Access Read write
Meaning The memory type of non-volatile parameters must be adjusted with
this parameter. The parameters will not be stored if the value is "0", the
deviceautomaticallychangestovalue"1"afterthenext"powerdown".
This value is the default value, the non-volatile parameters are always
stored.Value„2“deactivatesthestoring,alsooverthenextstartofthe
module.
Coding
0 off, curr. off / on at startup
1 on, always store
2 off, never store
Standard 1
Parameter Id-Text Name CANSDOIndex
os17 safety type 0x2091
Subindex 0
Object type Variable
Data length unsigned Word
Access Read only
Meaning Type of safety module
Coding
0
no safety module available
1
Safety module STO
2
Safety module STO with 0 Hz function