GB - 16
Control circuit
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
31
32
29
30
PIN Name Description Specications
21 COM Analog mass; Reference potential for analog inputs and outputs
22 ANOUT1 Analog output 1 U=0…±10 VDC (max. 11.5 VDC)
I
max
=10 mA
Ri = 100 Ω
Resolution= 11Bit + sign
23 COM like Pin 21
24 ANOUT2 Analog output 2 like Pin 22
25 R2-C Relay 2 Switching contact U
max
= 30 V DC
I = 0.01…1 A
max. switching cycles:
10
8
mechanical
500.000
at 1 A / 30 V DC
Ohmic load
26 R1-C Relay 1 Switching contact
27 R2-B Relay 2 NC contact
28 R1-B Relay 1 NC contact
29 R2-A Relay 2 NO contact
30 R1A Relay 1 NO contact
31 R3-C
2)
Relay 3 switching contact f=0 Hz is described in a sepa-
rate manual
32 R3-A
2)
Relay 3 NO contact f=0 Hz
1) The control release (terminal ST) is without function for units with safety function STO.
2) Relay 3 is only equipped at the version with 0Hz functionality. The function is described in
a separate manual.
2.1.5.3 Connection of the digital inputs
Connection of the digital inputs
with internal voltage supply with external voltage supply
12
11
6 8 10
5
4
3 7 9
12
11
6 8 10
5
4
3
7 9
+