Control circuit
2.1.5.5 Connection of the analog inputs
Examples for the connection of the analog setpoint input
2022
19
18
17
16
15
21
R = 0…3/5/10kΩ
2022
19
18
17
21
+
*)
0…±10Vdc
18
17
+
0…±20mA
4…20mA
*) Connect potential equalizing line only if a potential difference of >30 V exists
between the controls. The internal resistance is reduced to 30 kΩ.
Input
Factory setting of the setpoint inputs
Name PIN
AN1 17/18 analog setpoint setting 0…±10 Vdc
AN2 19/20
2.1.5.6 Connection of the analog outputs
Connection of the analog outputs
23
21
2224
Imax=10mA
0…10Vdc
I
max=10mA
0…10Vdc
Output Factory setting of the analog outputs
Name PIN open-loop operation closed-loop operation
AO1 22 Actual value display (CP01)
0…±400 Hz
Actual value display (CP01)
0…±4000 rpm
AO2 24 Apparent current 0…2•Iout