- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -
3-4 Message Communication
3-22
3
Communicating with the GT2 Series
The following settings are required to execute message communication with the DL-
EP1.
[DL-EP1]
The DL-EP1 does not require any setting.
[Scanner]
Set the applicable service, Class ID, Instance ID, Attribute ID, and service data, and
send the commands used for message communication. "Objects and Services"
(Page 3-25)
Refer to the scanner manual for details on the setting methods and applicable
commands.
The following lists the contents that can be executed by message communication
when the objects (DL Object) and services unique to the DL-EP1 are used.
(1) Reading data from a sensor amplifier
(2) Writing data to a sensor amplifier
(3) Issuing operation commands to a sensor amplifier
(4) Locking sensor amplifier operations
(5) Reading the number of decimal places from a sensor amplifier
(1) Reading data from a sensor amplifier
Message communication reads parameters from the DL-EP1 and the sensor
amplifier connected to the DL-EP1.
"(1) Reading parameters from a sensor amplifier" (Page 3-46)
Configuring Message Communication
Actions which can be Completed with Message Communication
Command
Response:
123456
GT2-7∗ Comparator values
(P. V. values): 123456
DL-EP1
Scanner
<Details of command>
Service code: 0EH
Class ID: 67H
Instance ID: 01H
Attribute ID: 0325H (805)
GT2-7
∗