3-4 Message Communication
3-27
3
Communicating with the GT2 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -
The following describes the objects usable by the DL-EP1.
Objects Usable by DL-EP1
Command
Response
DL
Object
Message
Router
Object
Connection
Manager
Object
Assembly
Object
Identity
Object
TCP/IP
Interface
Object
Ethernet
Link
Object
EtherNet/IP unit
Object Name Class ID Description
Reference
Page
DL Object 67H
This object provides the statuses of the DL-EP1 and
the sensor amplifiers connected to the DL-EP1 and
writes and reads parameters. This object is unique to
the DL-EP1.
3-31
Identity Object 01H
This object provides identification information,
general information and a reset service, etc.
5-19
Message Router
Object
02H
This object provides connection points for message
communication.
5-22
Assembly Object 04H
This object provides access to the devices via cyclic
communication. This object can be used to send data
to the devices that do not support cyclic
communication.
5-23
Connection
Manager Object
06H
This object is used for connection-type
communication.
5-25
TCP/IP Interface
Object
F5H
This object provides the structure for setting the TCP/
IP network interface. You can set an IP address,
subnet mask and gateway, etc., in this object.
5-27
Ethernet Link Object F6H This object provides Ethernet status information. 5-31