3-4 Message Communication
3-29
3
Communicating with the GT2 Series
- EtherNet/IP Compatible Network Unit DL-EP1 User’s Manual (GT2) -
Command processing order and error response
Check whether each ID is within the supported range in the following order:
Supplement for object processing
Get_Attribute_Single and Get_Attributes_All are executed, ignoring send service
data.
The service (Get_Attributes_All, Reset) that does not designate an attribute ID is
executed, ignoring Attribute ID.
If Set_Attribute_Single is designated for an attribute which cannot be written (Set),
"0EH" (Attribute not settable) is returned as the general status.
If Set_Attribute_Single for the writable attribute is designated and the writing size
is less than the attribute size, the general status "13H" (Not enough data) is
returned. If the writing size is greater than the attribute size, the service is
executed, ignoring the excessive data.
Class ID check
Yes
No
Instance ID check
Yes
No
Service check
Yes
No
Attribute ID check
Executes supported service process
Yes
No
Path Destination Unknown (05H)
returned as general status
Path Destination Unknown (05H)
returned as general status
Service not Supported (08H)
returned as general status
Attribute not Supported (14H)
returned as general status