2 Operation and Features 
Programming the Overvoltage Protection
36 E3632A User’s Guide
3 Enter the OVP menu and set the desired trip level.
LEVEL 32.0 V
You will see the above message on the display when you 
enter the OVP menu. Adjust the control knob for the 
desired OVP trip level. Note that you cannot set the trip 
levels to lower than 1.0 V.
4 Enable the OVP circuit.
OVP ON
You will see the above message after pressing 
.
5 Exit the OVP menu.
CHANGED
The  CHANGED message is highlighted for a second to show 
that the new OVP trip level is now in effect. If the OVP 
settings are not changed, NO CHANGE will be displayed. 
The power supply will exit the OVP menu and the display 
will return to the meter mode. Check that the OVP 
annunciator turns on.
Checking the OVP operation
To check OVP operation, raise the output voltage to near the 
trip point. Then very gradually increase the output by 
turning the knob until the OVP circuit trips. This will cause 
the power supply output to drop to near zero, the OVP 
annunciator to flash, and the CC annunciator to turn on. The 
OVP TRIPPED message also appears on the display.
Clearing the overvoltage condition
When the OVP condition occurs (the OVP TRIPPED message is 
shown on the display), the OVP annunciator flashes. When it 
was caused by external voltage source such as a battery, 
disconnect it first. The following steps show how to clear the 
overvoltage conditions and get back to normal mode 
operation. In the following steps, the display will go back to 
OVP TRIPPED if you let the display time- out after about 
several seconds.