Chapter 2: Front panel programming 
102  P/N 3102351-EN • REV 005 • ISS 28DEC18 
Panel programming 
The panel options to be configured include: 
  NAC circuits (“NACs”) 
  Annunciator class 
  Annunciator 
  Dialer and network (“CMS device”) 
•  Printer 
•  IP address (“IP”) 
•  Subnet mask (“MSK”) 
•  Gateway (“GWY”) 
Most options have a factory default setting that you can accept or change. See “Factory default 
settings” on page 42. 
Notes 
•  The option “CMS device” is only available if a dialer or network card is installed 
•  The option “Printer” is only available if a printer (RS-232) card is installed 
•  The options “IP”, “MSK”, and “GWY” are only available if a network card is installed 
To program panel configuration options: 
1.  Press the Menu button and choose Programming. 
2.  Choose Advanced Program and enter the level 2 password. 
3.  Choose Panel Configuration. 
4.  Program the options. 
NAC programming 
The NAC circuits connected to the system must be programmed with the type of NAC, label, 
correlation groups, and event notification. Each NAC must be programmed separately. 
Table 30: NAC programming options 
  Description 
  Select either Class A or Class B. 
Note: NAC 3 and 4 cannot be set to Class A. If NAC 1 and 2 are set to 
Class A, NAC 3 and 4 automatically configure to accept the Class A return.
  Set the NAC type to one of the following values. 
Continuous (silenceable or nonsilenceable): For strobes and notification 
appliances that generate a temporal pattern 
Temporal (silenceable or nonsilenceable): Universal 3-3-
for evacuation signals by NFPA 72. Used when notification appliances are 
not capable of generating a temporal pattern.