Appendix B: Worksheets 
P/N 3102351-EN • REV 005 • ISS 28DEC18  197 
Equation method 
Appliance operating voltage and current 
Regulated notification appliances have an operating range from 16 V to 33 V. Use 16 V as the 
minimum appliance voltage when using regulated notification appliances. 
When using special application notification appliances, refer to the installation sheets to 
determine the minimum appliance voltage required. 
What if there are different types of appliances in the NAC, and each type has a different 
minimum operating voltage? In this case, use the highest minimum voltage required by any 
appliance. 
The total current requirement for the appliances is the sum of the individual maximum currents 
drawn by each appliance when using FWR power. Use the maximum current for the appliance 
over the 16 V to 33 V range. 
If all appliances draw the same maximum current, the total current is the maximum current 
multiplied by the number of appliances. If different appliance types have different maximum 
currents, the total current is the sum of the maximum current for each appliance type multiplied 
by the number of appliances of that type. 
Wire resistance 
Typical wire resistances are shown in the following table. 
Table 46: Typical wire resistances 
  Resistance 
1-strand uncoated copper 
Resistance 
7-strand uncoated copper 
Ω per foot  Ω per meter  Ω per foot  Ω per meter 
  0.00193  0.00633  0.00198  0.00649 
  0.00307  0.01007  0.00314  0.01030 
AWG  0.00489  0.01604  0.00499  0.01637 
  0.00777  0.02549  0.00795  0.02608 
 
When performing these calculations, always refer to the actual cable supplier documentation 
and use the actual Ω/ft. (or Ω/m) for the cable being used. 
Calculating cable length 
1.  Calculate the total current (Itot) as the sum of the maximum operating currents for all the 
appliances. 
Itot = ΣIa 
Where: 
Σ = sum of all 
Ia = appliance maximum current