Appendix E: Releasing Module 
P/N 3102351-EN • REV 005 • ISS 28DEC18  249 
•  Don’t configure Disable members using the User key for correlation groups with panel 
events. 
•  Install a relay confirmation circuit to indicate when the release and prerelease circuits are 
active. 
•  Don’t power the REL from the panel. You must power the REL using a compatible power 
supply. See the GSA-REL Technical Reference Manual (P/N 387515-EN) for a list of 
compatible power supplies. 
REL fault messages 
Table 55 below lists the messages you may see for the REL on the panel’s LCD. 
Table 55: REL fault messages 
  Condition  LED  LCD message 
  Short  Monitor  Monitor 
Open  Trouble  Trouble 
Abort [1] 
Expanded message: Monitor Open 
  Short  Alarm  Pull station 
Manual [1] 
Expanded message: Pull station 
Open  Trouble  Trouble 
Manual [1] 
Expanded message: Pull station open 
Supervised 
Output 
(Prerelease_1)
 
Short  Trouble  Trouble 
Prerelease_1 [1] 
Expanded message: Supervised output short 
Open  Trouble  Trouble 
Prerelease_1 [1] 
Expanded message: Supervised output open 
 
Short  Trouble  Trouble 
Prerelease_2 [1] 
Expanded message: Supervised output short 
Open  Trouble  Trouble 
Prerelease_2 [1] 
Expanded message: Supervised output open