Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 43
Event notification
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > NET (1-8): No
Trouble > CID: 321 (NAC1), 322 (NAC2),
326 (NAC3), 327 (NAC4)
Disable > Printer: Yes
Disable > Dialer: Acct 1
Disable > NET: Yes
Disable > CID: 521 (NAC1), 522 (NAC2), 526 (NAC3),
527 (NAC4)
Test > Printer: Yes
Test > Dialer: Acct 1
Test > CID: 600
Test > NET
(1-8): No
Annunciator class: Class B
Annunciators (1-8)
Type: Off
Number expanders: None
Event notification
Trouble > Printer: Yes
Trouble > Dialer: Acct 1
Trouble > CID: 334
Trouble > NET (1-8): No
Swinger shutdown: Off
CMS device
Dialer
Type: Dual line
Acct 1 and 2
Account ID: FFFF
Primary receiver #: Blank
Secondary receiver #: Blank
Format: CID
Line 1 and 2
Dialing: Tone
Cut Duration/supervision: 120 sec.
Tone wait: 10 seconds
Call disconnect seconds: Off
Test frequency hours: 6
Send restorals: Yes
Retry time: 5 seconds
Retry count: 5
Event notification: Device
Test time: 03:11
Rings to answer: 5
Ring type: Any
Callback: Disabled
Callback #: Blank
Printer
Type: Unsupervised
Event notification
Trouble > Printer: Yes
Trouble > Coder: 00-00-00-00
Trouble > Dialer: Acct 1
Trouble > CID: 336
Trouble > NET (1-8): No
Lock remote read: No
AC voltage: 120
Network (receiver)
Enabled: No
Account ID: FFFF
IP: 192.168.1.254
TCP/IP port: 9999
Send restorals: Yes
Event notification: Device
Hello time: 25
Timeout: 40
Receiver #: 2
Line #: 2