Chapter 2: Front panel programming 
P/N 3102351-EN • REV 005 • ISS 28DEC18  79 
  Description 
Head: The base is controlled by the detector’s settings: 
•  The base activates when the detector goes into alarm, unless the detector is set for alarm 
verification. 
•  If the detector is set for alarm verification, the base activates when the detector goes into 
alarm verification. It does not restore, however, until the alarm restores. 
•  The base does not respond when the detector goes into prealarm no matter how the 
detector is configured. Also, the base only follows the primary element of a dual element 
detector. Any activation from a secondary element does not trigger the base.  
Example: When a PCOS/PCD on a sounder base has a follow set to Head, the base is 
only triggered when a smoke event is generated. The base does not trigger when a CO 
event is generated.  
•  Devices with the base set to follow Head cannot be placed in correlation groups. When a 
device base is set to follow Head, the base is removed as an output from any correlation 
groups to which it belongs. 
Alarm: The base activates its relay when the detector goes into alarm. The base does not 
restore until the alarm event has been restored. Any activation from a secondary element 
(Active3) does not trigger the base. For CO device operation, see Follow CO below. 
Alarm and verify (ALM+VFY): The base activates its relay when the detector goes into alarm 
verify and continues when the detector goes into alarm. The base does not restore until both 
events have been restored. 
Alarm and prealarm (ALM+PALM): The base activates its relay when the detector goes into 
prealarm and continues when the detector goes into an alarm. The base does 
both events have been restored. 
Riser: The base is triggered individually by the loop controller (sounder bases only). 
None: A correlation group triggers the base. This can be applied to both relay and sounder 
bases and is used for relay bases configured as latched output devices. 
  This option controls the conditions that will activate relay or sounder detector bases. Select 
Yes to allow the device’s secondary element (example CO) to activate the base programmed 
functions. 
Note: This option is not available for base follow types of Head, Riser, or None. 
  Select the device type based on the type of device you are programming. 
Refer to “Device type descriptions” on page 49 for a list of all possible device types. 
Adding devices 
To add a device to a programmed system: 
1.  Install the device on the system. 
The system recognizes the new device and displays a trouble event message that indicates 
that there is an unprogrammed device. 
2.  Press Enter. 
The device details screen is displayed.