Chapter 2: Front panel programming
P/N 3102351-EN • REV 005 • ISS 28DEC18 87
To add a delay to a correlation group:
1. Press the Menu button and choose Programming.
2. Choose Advanced Program and enter the level 2 password.
3 Choose Loop Configuration.
4. Choose Correlation Groups.
5. Enter the number of the correlation group. (Values range from 001 to 199.)
6. Choose Delay.
7. Enter the number of seconds the correlation group should wait. (Values range from 000 to
300.)
8. Choose Save.
Adding and removing panel events
The following panel events can be added to correlation groups in order to trigger outputs in
that correlation. The outputs activate at the beginning of the event and restore when the events
restore.
• Signal Silence
• Drill
• Common Alarm
• Common Supervisory
• Common Monitor
• Common Disable
• Common Trouble
• Local AC Power
• System AC Power
• Aux Power 1
• Aux Power 2
You can also configure Reset for a correlation group in two ways:
• Reset Activate: When an event is added to a correlation group without a configured time
delay, the output activates when the reset starts and restores when the reset ends. When
an event is added with a configured time delay, the output activates only after the delay
time is reached.
If the delay is greater than twenty seconds, the outputs will not activate, since the delay
time exceeds the reset duration.
• Reset Restore: When an event is added to a correlation group without a configured time
delay, active outputs in the correlation are restored when the reset starts and the end of the
reset activates the outputs, provided the device triggering the output is still active;
otherwise, the outputs will not activate. When programmed with a time delay, the outputs