10.3 How to calibrate pellet flue gas probe
Follow the procedure below to calibrate the flue gas temperature probe:
Press SET (no. 3) 5 times.
Set code "F9" in lower display using “temperature increase/decrease” keys (no. 1 or 2).
Press SET (no. 3) to confirm.
The lower display value (e.g. 22) represents effective probe temperature reading. This temperature can be
varied using “temperature increase/decrease” keys (no. 1 or 2).
Make reading correspond to room temperature detected by a thermostat of reference, if operation is
performed with stove off and cold.
Press SET (no. 3) to confirm.