TP-6694 7/18 Appendix 113
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
Charger Temperature
Compensation Slope (mV/_C)
S A
--40–0
(12 V)
-80–0
(24 V)
-30
(12 V)
-- 6 0
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Voltage Absorption
(V)
S A
13–15
(12 V)**
26–30
(24 V)**
14.25
(12 V)
28.5
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Voltage Bulk (V)
S A
13–15
(12 V)**
26–30
(24 V)**
14.25
(12 V)
28.5
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Voltage Equalize (V)
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A
14–16
(12 V)
28–32
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Voltage Float (V)
S A
13–14
(12 V)**
26–28
(24 V)**
13.25
(12 V)
26.5
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Current transformer ratio ]
S S 1-- 1200
ECM power S S 0--1 0
Engine cooldown delay S A 0--600 300
Engine (cyclic) crank on S A 10--30 15
Engine (cyclic) crank pause S A 1-- 60 15
Engine ECM start delay S A 0--300 0
Engine idle duration S A 0--60 60
Engine no. of (cyclic) crank
cycles
S S 1--6 3
Engine restart delay S A 1--10 10
Engine start aid delay S A 0--10 0
Engine start delay S A 0--300 0
Equalize Current Limit (A)
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A 1–5
Adjustable with
Charger Custom
Profile enabled.
Forced Charge Cycle Reset
S A
Active
Inactive
Inactive
Output Enable Reduced Out S A Fixed Active
Voltage regulator gain S R 1--255 128
Voltage regulator stability
adjust
S R 1--255 128
Voltage regulator, volts per
Hertz slope
S R 1--10 5
Voltage regulator, volts per
Hertz cutin frequency
S R 42--62 57.5
* Some functions require optional input sensors or are engine ECM dependent on some generator set models.
[ ECM inputs are engine manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the battery
charger operation manual.
ST--Short Term, LT--Long Term