TP-6694 7/18112 Appendix
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
Charger Automatic Equalize
Enable
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A
Active
Inactive
Inactive
Charger Charge Cycles
Between Auto Equalize Cycles
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A 0–99
Adjustable with
Charger Custom
Profile enabled.
Charger Custom Profile Enable
S A
Active
Inactive
Inactive
Charger Depleted Battery
Current Limit
S A 1–5 2
Charger Depleted Battery
Voltage Target
S A
4–12
(12 V)
18–24
(24 V)
10
(12 V)
20
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Equalize Stage
Duration (Min)
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A 60 – 480
Charger Manual Equalize
Cycle Activation
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A
Active
Inactive
Inactive
Charger Maximum Absorption
Time Threshold (Min.)
S A
60 – 360
60 – 600
(NiCad
only)
240
Adjustable with
Charger Custom
Profile enabled.
Charger Maximum Bulk Time
Threshold (Min)
S A 60 – 600 480
Adjustable with
Charger Custom
Profile enabled.
Charger Refresh Charge Cycle
Time (Hr)
S A
0,
23 – 672
335
Charger Return To Bulk State
Voltage Threshold (V)
S A
10–13
(12 V)**
20–26
(24 V)**
12.8
(12 V)
25.6
(24 V)
Adjustable with
Charger Custom
Profile enabled.
Charger Starter Battery
Topology
Note: Verify that the battery
topology is set correctly for the
battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S A
Default
FLA/VRLA
AGM
Gel
NiCad
Default
Charger System Battery
Voltage
Note: Verify that the system
voltage is set correctly for the
battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S A
System 12
VDC
System 24
VDC
12 VDC
Charger Temperature
Compensation Enable
S A
Active
Inactive
Inactive