TP-6694 7/18 Appendix 111
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
Engine started Engine Start Status Not adjustable
Engine stopped Engine Stop Status Not adjustable
EPS supplying load Emerg Pwr On Notice Not adjustable
File system error (controller
fault)
File Error Shutdwn Not adjustable
Generator running Gen Running Notice Not adjustable
Input/output (optional module
board) communication loss
OB1 Com Loss Not adjustable
Internal failure Intern Error Shutdwn Not adjustable
Measurement Units,
0--English, 1--Metric
Measurement Display DS A 0--1 1
Metering communication loss MeterCommLos
Shutdwn
Not adjustable
NFPA 110 alarm active NFPA Alarm Notice
Not in auto (master control
buttons)
Not In Auto Warning Not adjustable
Prime power application,
0--Standby, 1--Prime
Power Type DS A 0--1 0
Remote start Remote Start Status Not adjustable
System ready System Ready Status Not adjustable
System timer failed TimerErrorNotice Not adjustable
Generator Functions
AC sensing loss AC Sens Loss
Warning
Not adjustable
AC sensing loss AC Sens Loss
Shutdwn
Fixed 3 Not adjustable
Alternator protection Alt Protect Shutdwn Not adjustable
Ground fault input * Ground Fault Warning Not adjustable
kW overload
Total Power High
Shutdwn
Fixed
102%
standby,
112%
prime
Fixed 60 Not adjustable
Locked rotor (failed to crank) Locked Rotor
Shutdwn
S A 1--5 5
Overfrequency Freq High Shutdwn 102--140% 110% Fixed 10 Not adjustable
Overvoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) High
Shutdwn
S A 105--135% 120% 2--10 2
Power rating Pwr Rating DS S 10--5000 275
System frequency System Freq DS S 50--60 60
System voltage System Volt DS S 110--600 208
Underfrequency Frequency Low
Shutdwn
80--95% 90% Fixed
10 ST
60 LT
Not adjustable
Undervoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) Low
Shutdwn
S A 70--95% 80% 5--30 10
Voltage/phase configuration,
0--Single phase, 1--Single
phase dogleg, 2--three phase
wye, 3--three phase delta
SystemPhase DS S 0-- 3 2
Voltage regulator average
voltage adjustment
VR Volt Adj DS R 108--600 208
(Voltage) regulator
communication loss
RegCommLoss
Shutdwn
Not adjustable
SiteTech Read/Write Display Only
Charger Absorption Current
Termination Target (A)
S A 1–5 2