TP-6694 7/18110 Appendix
Description
Programmer-
Defined
Settings
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Controller Display
Message
Low engine oil level * Oil Level Low
Shutdwn
Not adjustable
Low fuel level (diesel models) * Fuel Level Low
Warning
0--100% 35% 0--10 10
Low fuel level (diesel models) * Fuel Level Low
Shutdwn
0--100% 5% 0--10 0
Low fuel pressure
(gas models) *
Fuel Press Low
Warning
Not adjustable
Low oil pressure
Oil Press Low
Warning
Fixed
(Fixed
inhibit)
5
(5
inhibit)
Not adjustable
Low oil pressure
Oil Press Low
Shutdwn
Fixed
(Fixed
inhibit)
5
(5
inhibit)
Not adjustable
No coolant temperature signal Temp Sig Loss
Shutdwn
Not adjustable
No oil pressure signal Press Sig Loss
Shutdwn
Fixed 5 Not adjustable
Overcrank
Over Crank Shutdwn Fixed
(30
inhibit)
Not adjustable
Speed sensor fault Spd Sens Flt Warning Not adjustable
General Functions
Alarm silence, 0--Auto only
(NFPA 110), 1--Always
AlarmSilenceMode S A 0-- 1 1
Aux. inputs 0--5 VDC, 1 analog Aux Input Warning 0--100% 100% 0--10 0
Aux. inputs 0--5 VDC, 1 analog Aux Input Shutdwn 0--100% 100% 0-- 10 0
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Warning
0--10
(0--30
inhibit)
0(0
inhibit)
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Shutdwn
0--10
(0--30
inhibit)
0(0
inhibit)
Backup parameters loaded Backup Pars Status Not adjustable
Battery charger 1
communication loss
Bat1CommLoss Not adjustable
Battery charger 2
communication loss
Bat2CommLoss Not adjustable
Battery charger fault *
(* does not apply to charger
GM87448)
Batt Chg Flt Warning Not adjustable
Battery charger identity conflict BatIdErr Not adjustable
Battery charger parameter
mismatch
ParMisatch Not adjustable
Battery fault Battery Flt Not adjustable
Chicago code active * Auto Locked Notice
Common fault Common Fault
Shutdwn
Not adjustable
Common warning Common Warng Not adjustable
Contrast (see 2.7.7 GenSet
System)
Contrast Display D A 1--10 5
Default parameters loaded Default Pars Warning Not adjustable
Emergency stop Emerg Stop Shutdwn Not adjustable
Enclosure temperature: high
shutdown
Enclsr Temp: High
Shutdwn
S R Fixed Active Fixed
5(20
inhibit)
Not adjustable
Engine cooldown (delay) active Eng Cooldown Notice
Engine start delay active Start Delay Notice