EasyManua.ls Logo

Kone KDL16 - Elevator Shaft Setup; Finalizing the Commissioning (MR Elevators)

Kone KDL16
40 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AS-11.65.037
30 (40) (A) 2009-10-16
KDL16
Maintenance Instruction
© 2009 KONE Corporation
All rights reserved.
Disclosure prohibited
12.2 Elevator shaft setup
12.3 Finalizing the commissioning (MR elevators)
Step Action Illustration/Note
1 Ensure that the elevator is in RDF mode.
2 Drive the car just below the bottom floor.
3 Check that the leds 61:U, 77:N and 77:S
are lit.
Led 61:N must not be lit. LCE leds 30 and/
or B30 must be lit.
4 Activate the setup mode from the controller.
Set Shaft setup (5_2) parameter to 1.
5 Switch elevator to normal mode. Elevator starts the setup drive upwards.
6 Watch floor numbers on LCECPU. Elevator is ready for the normal drive when
the car stops at the topmost floor, car
relevels and the LCECPU shows the number
of the topmost floor.
7 If the drive code 118 and related subcode is
displayed after setup, refer to KDL16
diagnostic codes, 972485D01.
Step Action Illustration/Note
1 Remove all the tools and waste material
from the work site.
2 Clean the site.
3 Return the elevator to normal.
Perform a test run for the elevator.
If the load weighing device is not working
correctly, make adjustment according to
APPENDIX C. (LWM + LCEVTC) or
APPENDIX D. (WR, Micelect).
4 Return the elevator to service.

Table of Contents