EasyManua.ls Logo

KRAL BEM 500 - Page 39

KRAL BEM 500
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 Troubleshooting
14.1 Fault table
Fault message Cause and elimination
8.06Alarm Bypass
valve activated. Check
volumeter!
Relay2 for collective error message is active, Relay1 for bypass valve has dropped.
o Check flowmeter for blockage.
o Optimize settings in the menu items3.13–3.16 .
In case of independent measurement with two flowmeters:
o If bypass function is not desired, 3.14Setting Limit value bypass Set to0 .
o Reset the bypass and group error message, see 1.10Display reset bypass and group error
message.
8.07Alarm Max. FlowB
exceeded. Check pick
up!
The maximum permissible flow rate was exceeded in flowmeterA.
o Limit the flow rate.
o Check flowmeter.
o Use a larger size.
o Check and eliminate an electromagnetic interference using an oscilloscope (e.g. terminate shield
to Gnd).
8.08 Alarm VolumeterA
orB outside the
temperature range!
At least one of the measured temperatures of the connected flowmeter lies outside the permissible
range.
o Adjust temperature range of the flowmeters, see 2.19Setting Minimum temperature volumeter
or 2.20Setting Maximum temperature volumeter.
o Limit the temperature in the system.
o Use suitable sensors.
o Use suitable flowmeters.
8.09Alarm analog
output1 or 2 scaling
exceeded!
The flow rate exceeds the maximum scale value of an analog output.
o Correct the scale, see 3.03Setting Scale max. analog output1 or 3.05Setting Scale analog
max. output2.
8.10Alarm pulse
output1 or 2 max.
frequency exceeded!
The maximum output frequency of Pulse output1 or2 has been exceeded.
o Correct the scale, see 3.09Setting Scale pulse output1 or 3.11Setting Scale pulse output2.
o Correct the pulse width, see 3.12Setting Pulse output pulse width setting.
The maximum frequency of a pulse output amounts to:
o Mode Encoder: 1/(4 x pulse width ins)
o Mode Independent: 1/(2 x pulse width ins)
8.11 Alarm Change of
direction B exceeded,
check 30/s signals!
A pick up at flowmeter A has failed.
This error message is only displayed at the setting Function pulse inputs Encoder, see 2.13Setting
Function pulse inputs
o Check pulse inputs channelA (terminal7+19):
a)Square wave signal at both inputs: >30 direction change/s
-or-
b)Square wave signal at an input: Strong vibration (in case of standstill of the flowmeter)
-or-
c)A pick up delivers no signal (with running flowmeter)
With c):
o Check the connection of the corresponding pick up.
o Check the position of the corresponding pick up in the dry sleeve.
o Replace the corresponding pick up.
8.12Alarm Change of
directionB exceeded,
check 30/s signals!
A pick up at flowmeterB has failed.
This error message is only displayed at the setting Function pulse inputs Encoder, see 2.13Setting
Function pulse inputs
o Check pulse inputs channelB (terminals30 +40):
a)Square wave signal on both inputs: >30 direction change/s
-or-
b)Square wave signal at an input: Strong vibration (in case of standstill of the flowmeter)
-or-
c)A pick up delivers no signal (with running flowmeter)
With c):
o Check the connection of the corresponding pick up.
o Check the position of the corresponding pick up in the dry sleeve.
o Replace the corresponding pick up.
8.13Alarm temperature
sensor failure
VolumeterA!
Temperature sensorA or Temperature inputA is defective.
o Check the sensor connection.
o Replace the sensor.
o Check the temperature input.
Operating instructions
OIE 12en-GB Edition 2020-03
39

Table of Contents

Related product manuals