8 Commissioning/Start-up/Shutdown
39 of 88
BoosterControl Advanced
Q
H
S
100%
Q
H
S
200%
Q
H
S
300%
Fig.9: Control with floating frequency inverter
H Head
Q Flow rate
S Setpoint
ü The system is operational.
ü BoosterControl Advanced has been connected correctly.
ü Date and time have been set. (ðSection8.3.2,Page34)
1. Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
2. Set the parameters for the suction side. (ðSection8.5.1,Page45)
3. Set the frequency inverter parameters. (ðSection8.4.6,Page44)
4. Note dry running protection settings. (ðSection8.5.1,Page45)
5. Set the following parameters:
Table31: Parameter settings for control with one frequency inverter
Parameter Description Possible values
3-2-2-6 Operating mode Hyamat V
3-3-1 Number of pumps connected
BoosterControl Advanced reboots; observe notes
1 ... 6
3-3-3 Configuration, discharge side
BoosterControl Advanced reboots; observe notes
Floating frequency inverter
6)
3-4-2-3 Number of pumps started up in the event of a sensor
failure on the discharge side
0 ... 6
3-4-2-4 Limitation of the maximum system load Number of pumps in operation × 100
%
6) A frequency inverter must be installed in the control cabinet and wired so that it can control any of the pumps.
BoosterControl Advanced switches the frequency inverter to another pump after each operation cycle.