8 Commissioning/Start-up/Shutdown
40 of 88
BoosterControl Advanced
Parameter Description Possible values
3-4-3-5 Enable/disable flow detection and accuracy of flow
detection
0 deactivated
1.. Measuring interval = 20 s
Permissible load change = ±2 %
…9 Measuring interval = 4 s
Permissible load change = ±18 %
3-4-3-5-1 Activate flow detection: Flow bandwidth 0-0,5 bar
3-4-3-5-2 Interval for flow measurement ("0" deactivates the
function)
0-60 s
3-4-3-5-3 Step height for detecting the zero flow 1..100%
3-4-3-4-4 Define maximum pump load ("0" deactivates the
function)
0.100%
3-5-1 System pressure setpoint 0 ... x kPa
7)
3-5-3 Pressure bandwidth: range above and below the
setpoint where pumps are not stopped or started.
Permissible symmetrical deviation from the setpoint.
0 ... 1000 kPa
3-5-5 Maximum setpoint 0 ... x kPa
7)
3-6-2 Limit for minimum runtime of pump 0 ... 999 s
3-6-4 Maximum pump runtime. After this period,
BoosterControl Advanced starts the pump with the
least operating hours
0 ... 356400 s
3-6-5 When one pump is running: start delay of each
pump that cuts in
0 ... 999 s
3-6-6 When more than one pump is running: stop delay of
the pumps
0 ... 999 s
3-12 Fault behaviour: specifies how the control system
should behave in the event of a fault
Cascade
Deactivation
7) x depends on the maximum value of the pressure sensor used.