10 Parameter list
BoosterControl Advanced
69 of 88
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-7-1.1.2 Month
Setting the month
1 1.. 12 1 12 Everybody Customer
3-7-1.1.3 Day
Setting the day of the week
1 1.. 31 1 31 Everybody Customer
3-7-2 Time
Setting the time
- - - - Everybody Customer
3-7-2.1.1 Time
Setting the time in the format HH:MM:SS
0 0.. 86399 0 86399 Everybody Customer
3-7-3 Check run mode
Basic setting for forced start (check run)
Interval Off,
Digital input,
Interval,
Day-based,
Week-based
- - Everybody Customer
3-7-4 Check run interval
Interval-controlled forced start (check run);
the pumps are started at fixed, defined
intervals.
86400 0.. 1000000 0 1000000 Everybody Service
3-7-5 Check run at
Day-controlled forced start (check run);
the pumps are started at a defined time
- - - - Everybody Customer
3-7-5.1.1 Hours
Hours for daily forced start (check run)
0 0.. 23 0 23 Everybody Customer
3-7-5.1.2 Minutes
Minutes for daily forced start (check run)
0 0.. 59 0 59 Everybody Customer
3-7-6 Check run at
Weekly forced start (check run): at a
defined time on specific days
- - - - Everybody Customer
3-7-6.1.1 Hours
Weekly forced start (check run): at a
defined time (hours) on specific days
_ 0.. 23 0 23 Everybody Customer
3-7-6.1.2 Minutes
Weekly forced start (check run): at a
defined time (minutes) on specific days
_ 0.. 59 0 59 Everybody Customer
3-7-6.1.3 Day
Weekly forced start (check run): at a
defined time on a specific day
Sunday Sunday,
Monday,
Tuesday,
Wednesday,
Thursday,
Friday,
Saturday
- - Everybody Customer
3-7-7 Check run duration
Specifying the duration of the forced start
(check run)
30 0.. 30 0 30 Everybody Service