10 Parameter list
68 of 88
BoosterControl Advanced
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-6-1 Opt. pump starts /h
Entering the optimal pump starts per hour.
The pump runtime is automatically
adapted
10 0.. 99 0 99 Everybody Service
3-6-2 Min. run time
Limit for minimum runtime of pump
180 0.. 999 0 999 Everybody Customer
3-6-3 Min. run time corr.
Correction value for minimum runtime of
pump
10 0.. 99 0 99 Everybody Service
3-6-4 Max. run time
Maximum pump runtime.
After the time has lapsed, the system
switches over to the next pump.
86400 0.. 604800 0 604800 Everybody Service
3-6-5 Start delay
Start delay of pumps if pressure remains
below setpoint
1 0.. 999 0 999 Everybody Service
3-6-6 Stop delay
Stop delay of pumps if pressure remains at
setpoint
1 0.. 999 0 999 Everybody Service
3-6-8 RDP delay
Stop delay following detection of dry
running occurrence
10 0.. 999 0 999 Everybody Service
3-6-9 High/low alarm delay
Time window for suppressing alerts when
system pressure is exceeded/undershot
60 10.. 999 10 999 Everybody Service
3-6-10 WSD 1 pulse length
Water flow detection 1, length of pulse in
seconds
4 0.. 99 0 99 Everybody Service
3-6-11 WSD 2 pulse length
Water flow detection 2, length of pulse in
seconds
4 0.. 99 0 99 Everybody Service
3-6-12 WSD 3 pulse length
Water flow detection 3, length of pulse in
seconds
4 0.. 99 0 99 Everybody Service
3-6-13 Sys. start up delay
Start delay following re-start
10 0.. 32 0 32 Service Service
3-6-14 Jockey min. run time
Limit for minimum runtime of jockey pump
0 0.. 999 0 999 Service Service
3-7 Time/Date
Date and time
- - - - Everybody Nobody
3-7-1 Date
Setting the date
- - - - Everybody Customer
3-7-1.1.1 Year
Setting the year
... 1970.. 2099 1970 2099 Everybody Customer