10 Parameter list
BoosterControl Advanced
67 of 88
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-5-1 Set point
Entering the pressure setpoint (system
pressure)
400 0.. 1000 0 1000 Everybody Customer
3-5-3 Bandwidth
Bandwidth within which the frequency
inverters remain at the same, constant
speed independent of pressure.
5 0.. 999 0 999 Everybody Customer
3-5-4 Accumulation press.
Procedure for increasing pressure in the
accumulator before the system stops
30 0.. 999 0 999 Everybody Customer
3-5-5 Max.set point
Limit value for maximum setpoint
1000 400.. 1000 400 1000 Everybody Service
3-5-9 Adapt. setpoint
Date/time-based alternative setpoint
400 0.. 1000 0 1000 Everybody Customer
3-5-10 Delta p Dynamic pressure compensation
Quadratic function for correcting the
setpoint
0 -999.. 999 -999 999 Everybody Customer
3-5-11 High pressure alarm
Upper limit value for maximum system
pressure
1000 400.. 1000 400 1000 Everybody Customer
3-5-12 High pressure action
Parameter for selecting action in case of
excessively high system pressure (stop
pumps or output message only)
Stop pumps Stop pumps,
message only
- - Everybody Customer
3-5-13 Low pressure alarm
Lower limit value for minimum system
pressure
0 0.. 400 0 400 Everybody Customer
3-5-14 Low pressure action
Parameter for selecting action in case of
excessively low system pressure (stop
pumps or output message only)
Stop pumps Stop pumps,
message only
- - Everybody Customer
3-5-15 Shut down RDP
Minimum suction-side pressure limit for dry
running protection
20 0.. 80 0 80 Everybody Customer
3-5-16 Reset RDP
Suction-side pressure for re-start following
dry running occurrence
80 20.. 999 20 999 Everybody Customer
3-5-17 Press. Flow Control
Lack-of-water fault is set if setpoint minus
pressure defined is undershot.
100 0.. 1000 0 1000 Everybody Service
3-6 Timer settings
Configuring the time parameters
- - - - Everybody Nobody