10 Parameter list
66 of 88
BoosterControl Advanced
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-4-5-2 Rated Freq
Rated frequency of pump
50 45.. 50 45 50 Everybody Service
3-4-5-3 Switch On Freq.
Start frequency of pump
49 31.. 50 31 50 Everybody Service
3-4-5-4 Switch Off Freq.
Stop frequency of pump
31 30.. 49 30 49 Everybody Service
3-4-5-5 Cubic setting
Cubic setting
- - - - Everybody Service
3-4-5-5-1 Power 1
Power 1 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-5-2 Power 2
Power 2 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-6 Linear setting
Linear setting of pump
- - - - Everybody Service
3-4-5-6-1 Power 1
Power 1 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-6-2 Power 2
Power 2 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-6-3 Power 3
Power 3 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-6-4 Power 4
Power 4 of pump
2 0.. 100 0 100 Everybody Service
3-4-5-7 Motor settings
Motor settings
- - - - Everybody Nobody
3-4-5-7-1 Rated Motor Power
Rated power of motor as per name plate
2 0.. 110 0 110 Everybody Service
3-4-5-7-2 Rated Motor Speed
Rated speed of motor as per name plate
1450 300.. 3600 300 3600 Everybody Service
3-4-5-7-3 Rated Freq
Rated frequency of motor as per name
plate
50 45.. 50 45 50 Everybody Service
3-4-5-7-4 Rated Current
Rated current of motor as per name plate
10 0,1.. 999 0,1 999 Everybody Service
3-4-5-7-5 Rated Cosphi
Rated cos phi of motor as per name plate
1 0,1.. 0,99 0,1 0,99 Everybody Service
3-4-5-8 Pump parameters
Pump settings
- - - - Everybody Nobody
3-4-5-8-1 Rated Pump Speed
Rated speed of pump for rated H/Q
characteristic curve
2900 300.. 3600 300 3600 Everybody Service
3-5 Pressure
Configuring the system pressure
- - - - Everybody Nobody