10 Parameter list
BoosterControl Advanced
65 of 88
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-4-3-23 Jog frequency
Speed in manual mode
50 30.. 50 30 50 Everybody Service
3-4-3-24 Jog ramp time
Ramp time
5 0,04.. 3600 0,04 3600 Everybody Service
3-4-3-25 Costing select
Selecting the manual mode
Digital and bus Digital input,
bus,
digital and bus,
digital or bus
- - Everybody Service
3-4-3-26 Start select
Selecting the start signal
Digital and bus Digital input,
bus,
digital and bus,
digital or bus
- - Everybody Service
3-4-3-27 Slip Compensation
Slip compensation
0 -400.. 399 -400 399 Everybody Service
3-4-3-5 No flow detection
Accuracy with which a minimum flow is
detected (procedure for stopping the
pumps)
- - - - Everybody Service
3-4-3-5-1 No flow bandwith
Bandwidth of flow detection
6 0.. 50 0 50 Service Service
3-4-3-5-2 No flow time
Flow detection time in seconds
16 0.. 60 0 60 Service Service
3-4-3-5-3 No flow step
Step height of flow detection in percent
1 1.. 50 1 50 Service Service
3-4-3-5-4 No flow max. power
Flow detection is active below this pump
load in percent
100 0.. 100 0 100 Service Service
3-4-4 WSD settings
Configuring water flow detection
- - - - Everybody Nobody
3-4-4-1 Nbr of refreshments
Number of water replacement cycles
30 0.. 99 0 99 Everybody Service
3-4-4-2 Refresh time span
Duration of water replacement procedure
in hours
24 0.. 999 0 999 Everybody Service
3-4-4-3 Average room temp.
Measured average ambient temperature
25 0.. 50 0 50 Everybody Service
3-4-4-4 Room temp. time span
Duration of ambient temperature
measurement in hours
24 0.. 999 0 999 Everybody Service
3-4-5 MPO settings
Configuring the multiple pump operation
functions
- - - - Everybody Customer
3-4-5-1 High Load Profile
Characteristic of pump
Cubic Linear,
Cubic
- - Customer Develop