SLC-220 User Guide Rev 2.0 June 2018
59
Default values:
Water: 15 (24 hours)
Oil: 1 (15 minutes)
High Oil: 1 (15 minutes)
Air: 5 (60 minutes)
Fail: 14 (12 hours)
Low Battery: 7 (120 minutes)
Note: This setting must be done to avoid too many messages sent to users, but should not be too
often for battery operated systems. If the SLC-220 is a Remote unit to SLR-220, the
intervals should be short enough to enable appropriate updates.
Note: This setting can also be done from the LCD (if installed).
6.1.5 Sensor Sample Interval
This determines how often the specific sensor will be turned on and sampled. This parameter can
also be set through SLC-Manager PC program. This is important for battery operated systems.
Message format:
CFGSMP,sensor index,Interval Index
sensor index: A single digit number describing the number of the sensor in the unit, from sensor
#1 till sensor #4.
Interval Index: Index between 0 and 7, taken from the table below.
Index
Interval
0
Continuous
sampling
1
30 seconds
2
1 minute
3
2 minutes
4
3 minutes
5
4 minutes
6
8 minutes
7
15 minutes
Example: CFGSMP,2,5
Sensor #2 will be sampled every 4 minutes.
Note: For battery operated sensors select 1 minute.
Note: This setting can also be done from SLC-Manager PC program or from the LCD (if installed).
Note: In firmware version 4.1 and up, this parameter is ignored.