Appendix B Supported Maximum Number of
Sensors and Actuators
The maximum number of sensors and actuators that can be managed per sensor port of a supported
managing product is 32 sensors or actuators. These sensors may be part of a "sensor package"
containing mulple sensors or actuators, such as a DX2-T1H1, which is 1 package with 2 sensors. The
maximum number of packages that can be managed per Sensor port of a supported managing device is
12 packages.
Calculaon examples for managed sensors/actuators:
A sensor package may contain more than one sensor/actuator, and each sensor or actuator is counted
as an individual funcon. You cannot exceed 64 funcons per sensor port.
For example:
A DX2‑T1H1 contains 2 sensors so it has 2 functions.
A DXD2C6 contains 6 sensors and 2 actuators so it has 8 funcons.
Tip for managed/unmanaged sensors:
To avoid exceeding the maximum of managed sensors/actuators per sensor port, you can manage
"paral" sensors/actuators of each DX/DX2 and unmanage the rest.