Page 35
301 Fulling Mill Road, Suite G ©Copyright 2015 by Legrand,
Middletown, PA 17057 Inc All Rights Reserved.
(800) 321-2343 www.legrand.us
For Honeywell Prestige IAQ 2.0 (RedLINK):
The following procedure outlines the standard configuration of the Honeywell Prestige® IAQ 2.0
Thermostat for use with the Legrand Intuity Home Automation System. Equipment installation
will be in accordance with the instructions provided by Honeywell.
Deadband Setup for Intuity:
A/C with Low Speed Fan
Setup 1 (if Overcooling Limit is set to 1˚)
1. Menu>Installer options>[Installer Code]>View/Edit Current Setup
2. View/Edit Current Setup>Dehumidification>Dehumidification Equipment>A/C with Low
Speed Fan>[Done]
3. View/Edit Current Setup>Dehumidification>Dehumidification - Overcooling Limit:
X˚>1˚>[Done]
4. View/Edit Current Setup>Heat/Cool Control Options>Deadband: X˚>2˚>[Done]
5. Return to the Main Menu. Setup Complete.
Setup 2 (if Overcooling Limit is set to 0˚)
1. Menu>Installer options>[Installer Code]>View/Edit Current Setup
2. View/Edit Current Setup>Dehumidification>Dehumidification Equipment>A/C with Low
Speed Fan>[Done]
3. View/Edit Current Setup>Dehumidification>Dehumidification - Overcooling Limit:
X˚>0˚>[Done]
4. View/Edit Current Setup>Heat/Cool Control Options>Deadband: X˚>3˚>[Done]
5. Return to the Main Menu. Setup Complete.
A/C with High Speed Fan
Setup 3
1. Menu>Installer options>[Installer Code]>View/Edit Current Setup
2. View/Edit Current Setup>Dehumidification>Dehumidification Equipment>A/C with Low
Speed Fan>[Done]
3. View/Edit Current Setup>Dehumidification>Dehumidification - Overcooling Limit:
X˚>1˚>[Done]
4. View/Edit Current Setup>Heat/Cool Control Options>Deadband: X˚>2˚>[Done]
5. Return to the Main Menu. Setup Complete.