iComfort Wi-Fi
®
7-Day Programmable Communicating Thermostat
Page 13
Heat Pump Airflow Settings
High Heat Pump Airflow
(CFM @ 100%)
Outdoor unit
tons
400CFM
Min
CFM
Max
CFM
25
Heat Pump
present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Low Heat Pump Airflow
(CFM @ lowest stage)
(See Note 2
at end of
table)
Min
CFM
Max
CFM
25
2+ stage Heat
Pump present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Other Parameters
Continuous Indoor Blower Airflow
DIP SW
(See Note at
end of table)
Min
CFM
Max
CFM
25
None
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Humidification Airflow
Same as
above
Min
CFM
Max
CFM
25
Humidifier present
1/2 HP blower
Min
CFM
Max
CFM
25 1 HP blower
Note 1: Minimum Outdoor Unit Cooling Stage as a percentage of High Cooling Airflow (value is rounded up to the closest number on 25 CFM resolution.
Note 2: Minimum Outdoor Unit Heating Stage as a percentage of High Heat Pump Airflow (value is rounded up to the closest number on 25 CFM resolution).
Note 3: All communicating Installer Parameters default CFM values based on DIP switch setting (non-communicating value) are calculated using the CFM
conversion tables and rounded up to closest number on 25 CFM resolution.
Table 7. System Devices > Thermostat
System
Heat Pump
Furnace
Thermostat
system devices
To adjust a setting, high
light it, then press Edit
edit
next
back
about
resetAll
Thermostat
Equipment Name
Press edit to change name (up to 35 characters may be used).
Note: Pressing the resetALL button will reset all custom parameter settings
back to factory default.
Temp Reading Calibration 0ºF -5ºF to 5ºF 1ºF
Humidity Reading Calibration 0% -10 to 10% 1%RH
Table 8. System Devices > Zoning Control
System
Heat Pump
Furnace
Thermostat
Zoning Control
system devices
To adjust a setting, high
light it, then press Edit
edit
next
back
about
resetAll
Zoning Control
Parameter Name Default Min. Max. Incr. Dependency
Zone 2 Temp Reading Calibration 0ºF -5ºF 5ºF 1ºF
Damper control module
installed
Zone 3 Temp Reading Calibration 0ºF -5ºF 5ºF 1ºF
Zone 4 Temp Reading Calibration 0ºF -5ºF 5ºF 1ºF
NOTE - More zoning parameters are available under system devices > system on page 9.