Table 10. Alert Codes and Troubleshooting
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
Alert
Code
PRIORITY
CONDITION
APPLICABLE
SYSTEM
COMPONENTS
ALERT TEXT
COMPONENT OR SYSTEM OPERA
TIONAL STATE AND TROU
BLESHOOTING TIP
HOW TO CLEAR
ALERT CODE
229 Minor
Furnace
The furnace control has
switched to high fire ignition be
cause the low fire pressure
switch did not close in the al
lowed time.
Furnace control switched to high fire
ignition because low fire pressure
switch did not close in allowed time.
No action is needed.
240 Moderate
Furnace
The furnace flame current is
low.
Check micro-amperes of the
flame sensor using thermostat di
agnostics.
Clean or replace the flame sen
sor.
Measure voltage of neutral to
ground to ensure good unit
ground.
Automatically clears
after a proper micro-
amp reading has been
sensed.
241 Critical
Furnace
The furnace flame is going out
while the furnace is heating.
Shut off gas.
Check for a gas valve leak.
Replace the gas valve if needed.
Automatically clears
when a heat call ends
successfully.
250 Moderate
Furnace
The furnace primary limit switch
is open.
Check for proper firing rate on fur
nace.
Ensure there is no blockage in
the furnace and the duct work.
Check for proper air flow.
If limit switch is not closed within
three minutes, the unit will go into
one hour WatchGuard mode.
Automatically clears
when a heat call ends
successfully.
252 Moderate
Furnace
The furnace discharge air-tem
perature is high.
Check temperature rise, air flow
and input rate.
Check for dirty air filter(s). .
Automatically clears
when a heat call ends
successfully.
270 Critical
Furnace
The furnace is in WatchGuard
mode. The furnace igniter can
not turn on the flame.
This is a five strike condition dur
ing a single demand.
Check for proper gas flow.
Ensure that igniter is lighting
burner.
Check flame sensor current.
Check for dirty filters.
Automatically clears
on successful ignition.
271 Critical
Furnace
The furnace is in WatchGuard
mode. The furnace low pres
sure switch is open.
This is a five strike condition dur
ing a single demand.
Check pressure (inches w. c.) of
low pressure switch closing dur
ing a heat call.
Measure operating pressure
(inches w. c.).
Inspect vent and combustion air
inducer for correct operation and
restriction.
Automatically clears
on successful ignition.
272 Critical
Furnace
The furnace low pressure
switch is open during run
mode.
The system will go into
WatchGuard mode.
Check operation of low pressure
switch to see if it is stuck open
during a heat call.
Measure operating pressure
(inches w. c.).
Inspect vent and combustion air
inducer for correct operation and
restriction.
Automatically clears
when a heat call ends
successfully.