Table 10. Alert Codes and Troubleshooting
Critical alerts are displayed on the Home screen, in the Home
owner alert button, and in the Installer alert button. Minor and
moderate alerts are found only in the Installer alert button.
Alert
Code
PRIORITY
CONDITION
APPLICABLE
SYSTEM
COMPONENTS
ALERT TEXT
COMPONENT OR SYSTEM OPERA
TIONAL STATE AND TROU
BLESHOOTING TIP
HOW TO CLEAR
ALERT CODE
436
Moderate /
Critical
Outdoor unit
Inverter heat sink temperature
exceeded limit.
This occurs when the heat sink
temperature exceeds the inverter
limit. Inverter will issue inverter
alert code 13 first and slow down
to try to cool the heat sink.
If temperature remains high, out
door unit will stop both compres
sor and fan – moderate condi
tion.
Antishort cycle is initiated.
If condition occurs five times with
in an hour, system will lockout –
critical condition.
Feedback from supplier tear
down of inverter indicates that the
screws that hold the inverter to
the inverter board were loose
causing poor contact between
these two components.
Tighten screws that hold the heat
sink to the inverter control board.
NOTE: Wait five minutes to all capaci
tor to discharge before checking
screws.
Moderate condition
will automatically
clear when the in
verter sends an
alarm clear mes
sage.
Critical condition is
cleared by discon
necting power to
the outdoor unit
and restart.
437
Moderate /
Critical
Outdoor unit
Heat sink temperature sensor
fault has occurred (temperature
less than 4 ºF or greater than
264ºF after 10 minutes of opera
tion).
When the temperature sensor de
tects a temperature less than
0.4ºF or greater than 264ºF after
10 minutes of operation.
Outdoor unit will stop both com
pressor and fan – moderate con
dition.
Antishort cycle is initiated.
If condition occurs five times with
in an hour, system will lockout –
critical condition.
Moderate priority
condition will auto
matically clear
when the inverter
sends an alarm
clear message.
Critical priority con
dition can be
cleared by discon
necting and recon
necting power to
outdoor unit to
restart.
438
Moderate /
Critical
Outdoor unit
The inverter has detected a PFC
circuit over-current condition.
The inverter has detected a pow
er factor correction (PFC) over
current condition. This may be
caused by a high load condition,
high pressure, or outdoor fan fail
ure.
Outdoor control will display the
code when the inverter has de
tected the error – moderate con
dition.
After three minutes, the inverter
will reset and the compressor will
resume operation.
If the error condition occurs 10
times within a 60 minute rolling
time period, the outdoor unit con
trol will lock out operation of the
outdoor unit – critical condition.
Possible issue is system running
at high pressures.
Check for high pressure trips or
other alert codes in room thermo
stat and outdoor control.
Moderate priority
condition is auto
matically cleared
when the inverter
sends a clear mes
sage.
Critical priority con
dition will automati
cally clear when in
verter is power cy
cled.