EasyManuals Logo

Lennox PRODIGY M2 User Manual

Lennox PRODIGY M2
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #69 background imageLoading...
Page #69 background image
17. Electronic Configure To Order (ECTO) Control Parameters
Page 69
PRODIGYT M2 UNIT CONTROLLER
Control Parameter
No. Name
DescriptionUnits
Control Value
Min. Default Max.
B, C, D, & E BOXES Block 0 VAV, CAVB, & MSAV Parameters (continued)
0.23
DO_Mode_
A133_(VAV
mode)
0 0 127 Option
A133 (w/DIP set to VAV) Digital Out Mode = X + 32*Y + 16*Z
Input source= X:
0− None. Output enables exhaust fan stage 2.
1− Compressor 1 duty cycle. (Compressor crankcase heater func-
tion.) On when OAT <= ECTO 0.24 and >= ECTO 0.25 seconds
have passed with compressor 1 off. Off when OAT > ECTO 0.24
+ 3 deg F (fixed deadband) or < ECTO 0.25 sec have passed
with compressor 1 off.
2− On when occupied.
3− On when blower on.
4− On when heating demand.
5− On when cooling demand.
6.− On when heating or cooling demand.
7− System RH (A55_P298_5 RH)
8− System IAQ. (A55_P298_3 IAQ)
9− System OAT (A55_P267_1/2 OAT)
10− AI1. (A133_P194−6).
11− AI2. (A133_P194−7).
12− AI3. (A133_P194−8).
13− AI4. (A133_P194−9).
14− AO1. (A133_P194−11).
15 AO2. (A133_P194−12).
Algorithm Y for input sources 7−15:
0− Hysteresis loop
On when input >= ECTO 0.24
Off when input < ECTO 0.24−ECTO 0.25
1− Window
On when input is in range; >= ECTO 0.24
and <= ECTO 0.24 + ECTO 0.25
(Fixed 3−count hysteresis loop on rising
and falling edges of window.)
2− Delayed−on.
On when input is >= ECTO 0.24
for >= ECTO 0.25 seconds.
Off when input is < ECTO 0.24 − 3.
(Fixed 3−count hysteresis loop on edge.)
3− Delayed−off.
On when input is >= ECTO 0.24.
Off when input is < ECTO 0.24 − 3
for >= ECTO 0.25 seconds.
(Fixed 3−count hysteresis loop on edge.)
Inversion Z:
0 − Output not inverted.
1 − Output inverted.
0.24−0.25
ON
OFF
OFF
0.24+0.25
0.24
O
N
OFF
ON
DELAY
0.25
0.24
OFF
ON
0.24
DELAY
0.25
OFF
0.24
Graphs indicate output not
inverted. See figure 33.
0.24
DO_SP_
A133_
(VAV mode)
0
0
0
0
132
−.05
0
127
5.0
996
100
51
0
2.5
255
10.0
2000
100
−31
0.5
5.0
Counts
R:Volts
I:ppm
P:%
Y:DegF
M:"w.c.
N:"w.c.
A133 (w/DIP set to VAV) digital output mode setpoint
0.25
DO_DB_A133_
(VAV mode)
2
0
16
2
1
64
0.01
0
13
.50
102
13
8
416
0.05
.25
255
10.0
2000
100
162
8160
1.0
5.0
Counts
R:Volts
I:ppm
P:%
O:DegF
D:Sec.
L:"w.c.
N:"w.c.
A133 (w/DIP set to VAV) digital output mode deadband or delay.
0.26
Supply_Static-
Sensor_Low_
Alarm_Check
30
30
40
40
101
101
Count
P:%
Supply Static Pressure Sensor (A30) connected at (A133_P195_6)
(TB18_6) alarm threshold. Blower percent speed before checking
sensor after a 20 second delay. A value of 101 disables the low
threshold or open" alarm trap.
table continued on next page

Table of Contents

Other manuals for Lennox PRODIGY M2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox PRODIGY M2 and is the answer not in the manual?

Lennox PRODIGY M2 Specifications

General IconGeneral
BrandLennox
ModelPRODIGY M2
CategoryController
LanguageEnglish

Related product manuals