Memory problems
v Follow the suggested actions in the order in which they are listed in the Action column until the problem is
solved.
v See the parts listing in the Hardware Maintenance Manual to determine which components are customer
replaceable units (CRUs) and which components are field replaceable units (FRUs).
v If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Symptom Action
The amount of system memory
that is displayed is less than the
amount of installed physical
memory.
1. Make sure that:
v No error LEDs are lit on the operator information panel or on the DIMM.
v Memory mirroring does not account for the discrepancy.
v The memory modules are seated correctly.
v You have installed the correct type of memory.
v If you changed the memory, you updated the memory configuration in the
Setup Utility program.
v All banks of memory are enabled. The server might have automatically
disabled a memory bank when it detected a problem, or a memory bank
might have been manually disabled.
2. Check the POST event log for DIMM error messages:
v If a DIMM was disabled by a systems-management interrupt (SMI), replace
the DIMM.
v If a DIMM was disabled by the user or by POST, run the Setup Utility
program and enable the DIMM.
3. Make sure that there is no memory mismatch when the server is at the
minimum memory configuration.
4. Add one pair of DIMMs at a time, making sure that the DIMMs in each pair
are matching.
5. Reseat the DIMMs.
6. Replace the DIMMs in step 5, one at a time, in the order shown, restarting the
server each time.
Multiple rows of DIMMs in a
branch are identified as failing.
1. Reseat the DIMMs; then, restart the server.
2. Replace the lowest-numbered DIMMs with identical known good DIMMs;
then, restart the server. Repeat as necessary. If the failures continue after all
identified pairs are replaced, go to step 4.
3. Return the removed DIMMs, one pair at a time, to their original connectors,
restarting the server after each pair, until a pair fails. Replace each DIMM in
the failed pair with an identical known good DIMM, restarting the server after
you reinstall each DIMM. Replace the failed DIMM. Repeat step 3 until you
have tested all removed DIMMs.
4. (Trained service technician only) Replace the system board.
Chapter 7. Troubleshooting 95

Table of Contents

Other manuals for Lenovo ThinkServer RD240

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lenovo ThinkServer RD240 and is the answer not in the manual?

Lenovo ThinkServer RD240 Specifications

General IconGeneral
Form Factor2U Rack
Processor Sockets2
ChipsetIntel 5520
ProcessorIntel Xeon 5600 series
StorageUp to 8 hot-swap 2.5" or 3.5" drives
RAID SupportRAID 0, 1, 10, 5
Networking2 x 1Gb Ethernet ports
Operating System SupportWindows Server, Red Hat Enterprise Linux, SUSE Linux Enterprise Server, VMware ESXi
Memory Slots12 DIMM slots