7
Commissioning
Using the keypad E82ZBC − Vector control
EDK82EV113 DE/EN/FR 8.1
L
126
Switch−on sequence Note
12. Activate the control mode "vector control"
(C0014 = 4)
Lenze setting: Linear V/f characterisitic control
(C0014 = 2)
2
000
a
bcd e
mno
p
qr
Hi
Lo
1
j
gfkih PS
001 4
z
y
wx
13. Adapt the voltage/current range to the analog
setpoint (C0034)
Lenze setting: 0, (0 ... 5 V/0 ... 10 V/0 ... 20 mA)
z
y
wx
0
000
abcd e
mno
p
qr
Hi
Lo
1
j
gfkih PS
0034
Set the DIP switch on the
standard−I/O to the same range (see
Mounting Instructions for the
standard−I/O)
14. Enter the motor data See motor nameplate
A Rated motor speed (C0087)
Lenze setting: 1390 rpm
B Rated motor current (C0088)
Lenze setting: Depending on the controller
Enter the value for the motor
connection type (star/delta) selected!
C Rated motor frequency (C0089)
Lenze setting: 50 Hz
D Rated motor voltage (C0090)
Lenze setting: Depending on the controller
Enter the value for the motor
connection type (star/delta) selected!
E Motor−cos (C0091)
Lenze setting: Depending on the controller
15. Start the motor paramter identification (C0148)
0
000
a
bcd e
mno
p
qr
Hi
Lo
1
j
gfkih PS
01 48
z
y
wx
Only when the motor is cold!
A Ensure that the controller is inhibited
misc001
20 28
X3
}
Terminal X3/28 = LOW
B Set C0148 = 1
Press in addition
C Enable the controller.
misc002
20
28
X3
l Terminal X3/28 = HIGH
l The identification starts:
– The segment Off
– The motor makes a
high−pitched tone. The motor
does not rotate!
D If the segment becomes active after approx. 30
s,
inhibit the controller once again
misc001
20 28
X3
}
l Terminal X3/28 = LOW
l Identification is completed.
l Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
(C0092)
l Measured and stored:
– Motor stator resistance
(C0084) = Total resistance of
motor cable and motor