Commissioning
Using the keypad XT EMZ9371BC − Linear V/f characteristic control
7
EDK82EV113 DE/EN/FR 8.1
135
L
Switch−on sequence Note
8. Set the minimum output frequency (C0010)
Lenze setting: 0.00 Hz
0 %
[f]
100 %
C0011
C0010
9. Set the maximum output frequency (C0011)
Lenze setting: 50.00 Hz
10. Set the acceleration time T
ir
(C0012)
Lenze setting: 5.00 s
[ H z ]
2
C 0 0 1 1
1
0
t
i r
t
i f
T
i r
T
i f
t
T
ir
+t
ir
@
C0011
f
* f
t
ir
= acceleration time wanted
11. Set the deceleration time T
if
(C0013)
Lenze setting: 5.00 s
T
if
+t
if
@
C0011
f
* f
t
if
= deceleration time wanted
12. Set the V/f−rated frequency (C0015)
Lenze setting: 50.00 Hz
100%
0
0 C0015
V
min
V
out
f
13. Set the V
min
boost (C0016)
Lenze setting: dependent on the controller type
The Lenze setting is suitable for all
common applications
14. Activate the motor temperature monitoring
(C0119) if a PTC or thermal contact is
connected to the terminal X2.2.
Lenze setting: switched−off
Setting possibilities: ( 148)
15. Setpoint selection e. g. via potentiometer at the
terminals 7, 8, 9
16. Enable the controller.
20
28
X3
misc002
Terminal X3/28 = HIGH
17. The drive should be running now CW rotation: X3/E4 = LOW
CCW rotation: X3/E4 = HIGH
If the drive does not start, press
) Note!
In the menu "Diagnostic" the most important drive parameters can be
monitored