7
Commissioning
Using the keypad XT EMZ9371BC − Vector control
EDK82EV113 DE/EN/FR 8.1
L
138
Switch−on sequence Note
14. Start the motor paramter identification (C0148) Only when the motor is cold!
A Ensure that the controller is inhibited
misc001
20 28
X3
}
Terminal X3/28 = LOW
B Set C0148 = 1
press
C Enable the controller.
misc002
20
28
X3
l Terminal X3/28 = HIGH
l The identification starts:
– The segment Off
– The motor makes a
high−pitched tone. The motor
does not rotate!
D If the segment becomes active after approx.
30 s,
inhibit the controller once again.
misc001
20 28
X3
}
l Terminal X3/28 = LOW
l Identification is completed.
l Calculated and stored:
– V/f rated frequency (C0015)
– Slip compensation (C0021)
– Motor stator inductance
(C0092)
l Measured and stored:
– Motor stator resistance
(C0084) = Total resistance of
motor cable and motor
15. Activate the motor temperature monitoring
(C0119), if a PTC or thermal contact is
connected to the terminal X2.2
Lenze setting: switched−off
Setting possibilities: ( 148)
16. Setpoint selection e. g. via potentiometer at the
terminals 7, 8, 9
17. Enable the controller.
20
28
X3
misc002
Terminal X3/28 = HIGH
18. The drive should be running now CW rotation: X3/E4 = LOW
CCW rotation: X3/E4 = HIGH
If the drive does not start, press
) Note!
In the menu "Diagnostic" the most important drive parameters can be
monitored